Error handling: Motor power OFF.
Error reset: Possible.
Description: A mismatch between the output current state and current feedback was detected at the gate power output section on the power supply unit control board (1VH).
Main causes:
-
The brake release switch was pressed when motor power was switched on.
-
The power supply unit control board is faulty.
-
The wiring between the X320 connectors (24V brake power supply system) on the power supply unit control board has a poor connector connection, open circuit, or similar fault.
-
A problem with the power supply unit power board.
-
A problem with the motor brake 24V power output system (X316 to X319, X312, X313) from the power supply unit.
Countermeasures:
-
Check whether the brake release switch is pressed when motor power is turned ON.
-
Replace the power supply unit.
-
Check the wiring to X320.
-
Replace the motherboard.
-
Check the motor brake 24V power output system from the power supply unit for abnormalities (short circuits, open circuits in wiring, etc.).