8277
Category: Alarm
Cause
- Drive U V W output phase loss or incorrect phase sequence
- Open drive U V W output wiring or open encoder wiring
- Mechanical factors cause motor stalling
- Servo drive gain too low
- Position command increment too large
- Fault threshold 6065h is too small for the operating conditions
- Servo drive / motor fault
Corrective action
- Run the motor without a load and check the wiring. Rewire correctly or replace the cable.
- Check the wiring. Rewire so that the servo motor power cable and drive power cable UVW correspond individually. Replace with a new cable if necessary and ensure secure connections.
- Using the Inovance drive commissioning platform or panel display, confirm the operating command and motor speed (200B-01h). Operating command in position mode: 200B-0Eh (input position command counter). Operating command in speed mode: 200B-02h (speed command). Operating command in torque mode: 200B-03h (internal torque command). Confirm whether the operating command is not 0 while motor speed is 0 in the corresponding mode. Investigate mechanical causes.
- Check servo drive position-loop and speed-loop gains: First gain: 2008-01h
2008-03h. Second gain: 2008-04h2008-06h. Perform manual or automatic gain adjustment. - Position control mode: ◆CSP mode: Check gear ratio 6091-01h/6091-02h, determine the position command increment corresponding to one synchronization cycle, and convert it to speed information. Reduce the position command increment per synchronization cycle; add a position ramp when planning commands in the host controller. ◆PP mode: Check gear ratio 6091-01h/6091-02h and determine 6081h (profile velocity). Reduce 6081h or increase acceleration/deceleration ramps (6083h,6084h). ◆HM mode: Check gear ratio 6091-01h/6091-02h and determine 6099-01h and 6099-02h. Reduce 6099-01h and 6099-02h or increase the acceleration/deceleration ramp (609Ah). Reduce the gear ratio as appropriate.
- Confirm whether position deviation fault threshold 6065h is set too low. Increase the 6065h setting.
- Use the oscilloscope function of the Inovance drive commissioning platform to monitor operating waveforms: Position command, position feedback, speed command, torque command. If the position command is nonzero but position feedback remains zero, replace the servo drive / motor.