1610
Category: Alarm
Cause
- Drive EtherCAT communication synchronization mode does not match the host controller synchronization mode setting
- Host controller synchronization mode is configured as DC SYNC0, but the DC clock is not enabled
- EtherCAT synchronization mode is neither DC SYNC0 nor Free Run; the 0x1C32.01 setting is incorrect
Corrective action
- Ensure that the drive and host controller synchronization mode settings match
- If synchronization mode is configured as DC SYNC0, the DC clock must be enabled
- Avoid synchronization modes other than DCSYNC0 and Free Run