Description
The mechanical unit arg is not configured correctly according to the IndCnv function.
Consequences
Program execution stops.
Possible causes
mechanical unit arg contains multiple units.
The monomer connected to arg is not of type ' FREE_ROT '.
The cell connected to arg is not defined as a Indexing Move (indexed movement) cell.
Recommended actions
Make sure the mechanical unit arg contains only one unit.
Make sure that the system parameter "Mechanics (mechanical)" in the Motion (action) subject and Single (single) type is of type "FREE_ROT".
Make sure that the system parameter "Indexing Move (indexed movement)" in the Motion (action) subject and Single Type (single type) type is of type "Yes (yes)".