Error handling: Motor power OFF.
Error reset: Not possible.
Description: There is an abnormality such as an open circuit in the circuit carrying regenerative current.
Main causes:
-
A problem with the power supply unit power board.
-
The reactor in the reactor unit is faulty (open circuit).
-
An open circuit in the UVW harness connected between the power block for the power regeneration axis and reactor unit.
-
A problem with the power block for the power regeneration axis.
-
A problem with the servo board.
Countermeasures:
-
Replace the power regeneration unit.
-
Check the reactor unit or the wiring between the power module for the power regeneration axis and the reactor unit, and replace the wiring if necessary.
-
Replace the servo amplifier unit.