[Cause]
1. An emergency stop occurred on the control device of a teaching pendant sharing group.
2. An emergency stop occurred because the control device of a teaching pendant shared group was not powered on.
3. An emergency stop occurred because the safety function based on FL-net did not operate correctly.
4. [An emergency stop occurred due to an error in the teaching pendant sharing group setting.
[Countermeasure]
1. Eliminate the cause of the teach pendant emergency stop, operation panel emergency stop, or external emergency stop of the control device of the teach pendant sharing group.
2. Please turn on the power of all control devices in the teach pendant sharing group.
3. Please confirm the settings of the safety function and teach pendant sharing function based on FL-net.
4. Please confirm the setting of the teaching pendant sharing function.