2092
Category: Warning
Cause
- For a 200V servo unit, AC supply voltage is 140V or below; for a 400V servo unit, AC supply voltage is 280V or below.
- Supply voltage drops during operation
- A momentary power interruption occurs.
- The servo unit fuse is blown.
- Servo unit fault.
Corrective action
- Adjust supply voltage to the normal range.
- Increase power supply capacity.
- If the momentary power interruption hold time (Pn509) was changed, set it to a smaller value.
- Replace the servo unit, connect a reactor, and then use the servo unit.
- The servo unit may be faulty. Replace it.