Description
At startup, the YRC1000 transfers the parameters required to operate the ASF01 board and SDCA01 board from the ACP01 board. This alarm occurs if the transfer fails.
Subcode description
An error occurred during the
parameter/file transfer to the 7th
servo board.
Causes and remedies
| Cause | Remedy |
|---|---|
| Software (incorrect setting) | Check the following settings. • Control group setup in maintenance mode • Rotary switch setting on the SDCA01 board for the corresponding station number (SV#7) (6) |
| Cable (abnormal) | 1. Turn the power off and back on. 2. If the alarm recurs, check that the following cables and connectors are connected and fully inserted. • Cable for connector CN509 on the SDCA01 board • Cable for connector CN515/516 on the SDCA01 board • Cable for connector CN111 on the AIF01 board • Cable for CN155 on the CPS control power supply unit |
| SDCA01 board (abnormal) | 1. Turn the power off and back on. 2. If the alarm recurs, replace the SDCA01 board. Save CMOS.BIN before replacing the board. |
| AIF01 board (abnormal) | 1. Turn the power off and back on. 2. If the alarm recurs, replace the AIF01 board. Save CMOS.BIN before replacing the board. After replacing the AIF01 board, load CMOS.BIN saved before the alarm occurred. |
| Other | If the alarm occurs again after implementing the countermeasures, contact our service department and describe the circumstances when CMOS.BIN was saved (operating procedure, etc.). |