1789
Category: Alarm
Cause
Conditions:
- Main circuit voltage is below the specified voltage. The abnormality type defaults to Warning; to change it to Alarm, set P2.066 [Bit 9] to 1.
- DC Bus voltage is less than P4.024× √2. Causes:
- Main circuit input voltage is below the rated permitted voltage.
- No main circuit input voltage.
- Incorrect power input (incorrect supply system).
Corrective action
- Reconfirm the voltage wiring and check whether the main circuit input voltage wiring is normal.
- Reconfirm the power switch and use a voltmeter to check whether the main circuit voltage is normal.
- Use a voltmeter to check whether the supply system matches the specifications and whether the correct voltage source or a series-connected transformer is used. Clear AL003 according to the P2.066 [Bit 2] setting:
- If P2.066 [Bit 2] is set to 0, clear the alarm through DI.ARST after voltage recovers.
- If P2.066 [Bit 2] is set to 1, the alarm clears automatically after voltage recovers.