Description
An error occurred in the independent control startup operation.
Subcode description
An attempt was made to startup
the control group where IO
speed control is activated by a
job.
Causes and remedies
| Cause | Remedy |
|---|---|
| Software (incorrect setting) | 1. Reset the alarm. 2. Check the configuration of the IOSPDCTRL motion settings. A control group whose job start setting is Enabled cannot be used. 3. Adjust the job to avoid starting the control group during IO speed control. |
| Other | If the alarm occurs again after implementing the countermeasures, contact our service department and describe the circumstances when CMOS.BIN was saved (operating procedure, etc.). |