[Cause]
Recipe operation from PLC failed. This may be due to the following reasons:
1. DI or GI was not input from the PLC within the wait instruction time limit.
2. The GI value input from the PLC is invalid.
[Countermeasure]
For their respective reasons, the response is as follows:
1. After receiving DO or GO from the control device, enter a signal from PLC within the time limit of the stand-by command.
2. Input the following values to GI.
Created as '1 '
• Delete as "3"
Save as "4"
• Read with "5"
"6" at output
7 at input
• 8 for change of prescription
For details of the handshake with the PLC, refer to PK_PLC_RECIPE_OPERATION.TP.