8476
Category: Alarm
Cause
- Momentary drop in supply voltage
- Power was switched off during parameter writing
- The number of parameter writes exceeded the maximum
- Malfunction caused by noise from the AC supply, grounding, static electricity, etc.
- Gas, water droplets, cutting oil, etc. caused component failure inside the servo unit
- Servo unit fault
Corrective action
- Measure the supply voltage and confirm the power-off duration: Set the supply voltage within the specified range and initialize parameter settings (Fn005).
- Measure the supply voltage and confirm the power-off duration: Initialize parameter settings (Fn005), then enter the parameters again.
- Confirm whether the host device changes parameters frequently: The servo unit may be faulty. Replace the servo unit. Change the parameter writing method.
- If the alarm persists after repeatedly powering on, noise may be the cause: Take measures against noise interference.
- Check the installation environment: The servo unit may be faulty. Replace the servo unit.
- If the alarm persists after repeatedly powering on, a fault may have occurred. The servo unit may be faulty. Replace the servo unit.