8100
Category: Alarm
Cause
Condition: an error occurred during regeneration. Causes:
- Incorrect regenerative resistor selection or no external regenerative resistor connected.
- No regenerative resistor is used, but the user has not set the regenerative resistor capacity parameter (P1.053) to zero.
- Incorrect parameter settings (P1.052, P1.053).
Corrective action
- Verify the regenerative resistor connection, recalculate its resistance, and correctly reset P1.052 and P1.053. If the alarm persists, return the drive to the original manufacturer.
- If no regenerative resistor is used, set regenerative resistor capacity (P1.053) to zero.
- Correctly reset and verify the regenerative resistor resistance (P1.052) and capacity (P1.053) settings. Reset the alarm.