Description
In drive module arg, the link voltage of rectifier unit DC at unit location arg exceeds the upper limit.
Consequences
The system cannot operate until the fault is corrected, and the system will enter the "system interruption" (SYS HALT) state.
Possible causes
Bleeder resistor not connected or defective.
Recommended actions
Disconnect the bleeder, check the cable and measure the bleeder resistance value.